you are here > Lines Carried > American Electrical > DIN Rail Mounted Power Supplies > Slim Line

American Electrical, Inc. DIN Rail Mounted Power Supplies - Slim Line

 

 

 

 

DIN Rail Mounted Power Supplies - Slim Line

Vertical

Horizontal
Technical
Wide Range Compact Housing - 20A, 3ph only 3.39 inches long; Horizontal Mounting - up to 40A, 3 phase
Output 24V / 1.25 to 20A - Single phase; 24V / 10, 20, and 40A - 3 phase
Universal Input 115 / 230 VAC; 3 X 340 / 550 VAC
Load Sharing Parallel operation; Redundancy
High Efficiency Typical 90%
Increased Operating Temperature 100% at 140ºF
Status Indication Power ON indication; Overload Status LED
Touch Safe Power Entry Covered power entry; Convenient customer input terminals
Approvals UL / CSA and EN
Description Part No. Input Volts (VAC) Phase Output Volts (VDC) Output Current (Amps) Power (Watts) Dimensions L x W x H (inches)
Slim Line F2400125 115*/230 1 24 1.25 30 1.77 x 2.83 x 4.13
F240050S 115*/230 1 24 5 120 2.76 x 5.20 x 5.47
F24010S 115*/230 1 24 10 240 2.76 x 5.81 x 6.46
Slim Line 3 Phase F24010S-3 3x 340-550 3 24 10 240 3.18 x 6.02 x 6.29
F24020S-3 3x 340-550 3 24 20 480 3.99 x 8.94 x 6.81
Horizontal F240025 115*/230 1 24 2.5 60 4.25 x 4.84 x 2.56
F240050 115*/230  1 24 5 120 5.79 x 4.84 x 3.39
 
F24010 115*/230 1 24 10 240 8.07 x 4.84 x 3.39
F24020 195-265 1 24 20 480 9.45 x 6.02 x 3.39
Horizontal F24020-3 3x 340-550 3 24 20 480 9.45 x 6.02 x 3.39
  F24040-3 3x 340-550 3 24 40 960 11.50 x 7.28 x 5.12
* Indicates Standard Voltage Inputs

Technical Data

Regulation

Line regulation < 0.2% with Uin± 15%
Load regulation < 1% with 0 A -> >Inom
Dynamics < 2 ms with 10<-->90% Inom peaks < 2%

Protection and Monitoring

Current Limitation Protection against continuous short circuit
Overload protection Yes
Non-load protection Yes
Overvoltage protection Yes

Safety

Output VDE 0805 / EN 60950 / IEC 950 / UL1950 safety voltage (SELV) acc. to EN 60950
protective system class I / Class II at 149002-31001149002-21001
Degree of protection IP 20
Leakage current (1.25A / 2A) < 0.25 mA (47-63 Hz line frequency)
Leakage current (5A / 10A) < 0.75 mA (47-63 Hz line frequency)
Leakage current (20A / 40A) < 3.50 mA (47-63 Hz line frequency)

EMV - Certified

RFI suppression Emission (EN 50081-1/-2) EN 55011 / EN55022 class B Immunity (EN 50082-1, EN 61000-6-2)
Static Discharge ESD acc. to EN 61000-6-2
IEC 1000-4-2 8kV contact discharge; 15kV free air discharge
Electro-magnetic fields acc. to EN 61000-4-3
IEC 1000-4-3 10V/m
Burst acc. to EN61000-4-4
IEC 1000-4-4 4kV input; 2kV output / AC-coupled
Surge acc. to EN61000-4-5
IEC 1000-4-5 4kV asymmetric; 4kV symmetric
Form of electrical interference IEC 1000-4-6 acc. to EN 61000-4-6; 10 V, 150 kHz ... 80 MHz
Operational Data
Temperature range -10ºC / 14ºF to +70ºC / 158ºF with free convection
Power derating 2.5% / K from +60ºC / 140ºF (see diagram)
Storage temperature -25ºC / -13ºF to +85ºC / 185ºF
Static Discharge ESD acc. to EN 61000-6-2
IEC 1000-4-2 8kV contact discharge

15kV free air discharge

Installation

Installation Easy access mounting bracket for rail DIN EN 50022-35
Mounting Position Upright with input terminals on top. Output terminals underneath.

 

We have attempted to present the information about our vendor's products on this website in a straight-forward manner. We offer this information as accurate at the time of publication. Specifications are subject to change without notice. Electro-Stock, Inc. is not responsible for inadvertent errors.

About UsFAQServicesTerms & ConditionsPolicies

Since 1983   

Hours: Monday through Friday 8:30am through 4:00pm CST - Leave Messages On Voice Mail After Hours.
Phone: 630-682-1542 
        
Order Line: 800-876-1152 (USA Only, Not Illinois)

Email: sales@electrostock.com         Mail & Remit To: 1218 E. Wilson Ave. Wheaton, IL 6018
9-6748 USA

 Home | Contact | © 1996 - 2012 Electro-Stock, Inc | Original Design by www.mitchinson.net